_AlertIE

Chauvin-Arnoux | CA6030

Controller of differential circuit breakers (RCD) and ground loop, Earth without rods

Chauvin-Arnoux
Reference : CARCA6030
Purchase Order Reference : P01191511
Brand : Chauvin-Arnoux
Test sur différentiels de types standard, sélectif, A ou AC.
5 calibres fixes 10/30/100/300/500mA + un calibre réglable de 6 à 650mA.
Test de non-disjonction / mesure du temps et du courant exact de déclenchement.
Mesure de terre sous tension : boucle de terre et terre 1P (sans piquets).
Test du sens de rotation des phases (2 ou 3 fils).
TTCHT
Quantity
Expédié sous 2 semaines
Quick quote for this product
Quick quote for this product
Details

C.A 6030

 
 
Cat. III 600V
NEW!
For complete and accurate testing of differential circuit-breakers
Innovative and particularly convivial. the C.A 6030 RCD tester combines optimum ease of use with enhanced metrological performances for the testing of protection systems and compliancy of installations with european and international standards NF C 15-100. VDE 0100. NIN/NIV. IEEE 16th. ÖVE EN-1.

  • Direct and safe connection to installation mains
  • Reliable measurements thanks to automatic permutation of L and N inputs if conductors are reversed at socket connection
  • Automatic installation voltage and frequency measurement
  • Tests standard. selective. A and AC type differentials
  • 5 fixed calibres 10/30/100/300/500mA + 1 calibre adjustable from 6 to 650mA
  • Checks circuit-breaker trips / trip time measurement (pulse or ramp mode) and exact trip current (ramp mode)
  • Power-on ground measurement: ground loop and 1P ground
  • Current and leakage current measurement clamp (option)
  • Phase rotation test (2 or 3-wire)
  • Programmable alarms. date-time recording of measurement readings. data print-out using standard printer. direct transfer of data to PC (transfer application included as standard)
  • Large backlit display / "hands free" pouch
  • Battery operated; autonomy: 2000 tests
  • Dimensions: 270x250x180mm ; weight : 900g
  • Product Details
    41-Standard Manufacturer Warranty 1 YEAR
    326-Differential type AC
    327-Differentials sensitivity (mA) 10 mA | 30 mA | 100 mA | 300 mA | 500 mA | 650 mA | Adjustable range
    119-Safety Level CAT I | CAT II | CAT III
    36-Additional Characteristics Power-on earth measurement: earth loop and 1P earth
    132-Package includes
    • Sacoche "tour du cou" avec une sacoche d'accessoires:
    • 1 cordon secteur, 1 cordon 3 fils, 3 pointes de touche / 3 pinces crocodile, 1 notice de fonctionnement en 5 langues 1 logiciel de transfert de données, et 1 cordon de communication
    35-Dimension (HxWxD) (mm) 270x250x180 mm
    13-Net Weight 900 g