Chauvin-Arnoux | CA1631
Process Calibrator, mA/mV/V sourcing
Calibrateur de process, source mA/mV/V
SOURCES:
Courant: 4-20 mA DC.
Précision: 0.015%.
Tension: 0-100 mV, 0-20 V DC.
Précision: 0.02%.
Alimentation en boucle: 24V.
MESURES:
Courant: 0-24 mA DC.
Tension: 0-100 mV, 0-20 V DC.
SOURCES:
Courant: 4-20 mA DC.
Précision: 0.015%.
Tension: 0-100 mV, 0-20 V DC.
Précision: 0.02%.
Alimentation en boucle: 24V.
MESURES:
Courant: 0-24 mA DC.
Tension: 0-100 mV, 0-20 V DC.
Details
CA 1631
Process Calibrator
Compact and simple to use. the C.A 1631 calibrator is equipped with a wide screen for comfortable reading..
The C.A 1631 can be used to measure and supply a DC current loop from 0 to 24 mA with 0.015% accuracy and a DC voltage between 0 and 20 V with an accuracy of +/- 0.02 %.
When used as a battery-powered stand-alone instrument. it offers a long battery life in the field. When connected to the mains. it can be used continuously without any time limit!
The C.A 1631 can be used to measure and supply a DC current loop from 0 to 24 mA with 0.015% accuracy and a DC voltage between 0 and 20 V with an accuracy of +/- 0.02 %.
When used as a battery-powered stand-alone instrument. it offers a long battery life in the field. When connected to the mains. it can be used continuously without any time limit!
DC voltage input and output specifications
Calibre Resolution Accuracy ± (% of reading + counts)
100 mV 0.01 mV 0.02 % + 3
20 V 0.001 V 0.02 % + 3
Input impedance: 2 MΩ (rated value). < 100 pF
Protection against overvoltage: 30 V
Current delivered by rated voltage: 1 mA
DC current input and output specifications
Calibre Resolution Accuracy ± (% of reading + counts)
24 mA 0.001 mA 0.015 % + 3
Protection against overloads: 125 mA/250 V quick-response fuse
Display as percentage: 0 % = 4 mA. 100 % = 20 mA
Source mode: 1.000 Ω load at 20 mA for battery voltage ≥ 6.8 V. (700 Ω at 20 mA for a battery voltage
between 5.8 and 6.8 V)
Simulation: external loop voltage condition: 24 V (rated value). 30 V maximum. 12 V minimum.
Loop voltage supply: 24 V ± 10 %
Product Details
41-Standard Manufacturer Warranty | 1 YEAR |
420-Measures ranges |
|
421-Generated ranges |
|
411-Measurement/generate (type) | mA | mV | V |
561-Loop power | 24V |
24-Accuracy (%) | Sourcing: 0.015% (mA); 0.02% (mV, V) Measures: 0.02%(mV, V); 0.015% (mA) |
132-Package includes | Delivered with 2 pairs of test wires and crocodile clip, 6 AAA 1.5 V batteries,1 operating manual in 5 languages and 1 carrying bag |
35-Dimension (HxWxD) (mm) | 205 x 97 x 45 mm |
13-Net Weight | 472 g |
Associated Guides